DGUV Information 203-077 / Guide selecting PPE in thermal hazards due to electric fault arcing

DGUV Information 203-077
Guide selecting PPE in thermal hazards due to electric fault arcing

ID 24964 | 22.11.2025 / Deutsche Gesetzliche Unfallversicherung 2021

DGUV Information 203-077
Thermal hazards due to electric fault arcing Guide for selecting  personal protective equipment
_________

This DGUV Information brochure is intended to support employers in their selection of suitable personal protective equipment (e.g. protective clothing, head and face protection and gloves) against the thermal effects of an electric fault arc (PPEaA).

Persons working on or in the vicinity of live electrical equipment are, in principle, exposed to hazards associated with electric fault arcing. Electric arcs are rare, yet cannot be eliminated completely in the working environment, meaning that persons therein will require reliable protection. Arcing is not only induced by short circuiting, but can also occur when two current-carrying components are separated from each other (e.g. installation/removal of circuit protectors while under load).
_________

The T-O-P principle for occupational safety should be used when evaluating thermal hazards and determining the measures to apply against electric fault arcing. This means that the use of personal measures (PPEaA) is viewed as being subordinate to technical and organizational measures. PPEaA is intended to minimize the remaining residual risk after the technical and organizational measures aimed at preventing an electric arc occurrence have been implemented.
_________

Depending on the electrical network and equipment configuration, electric arcing can be extremely hazardous:

- High levels of thermal energy.
- Shock waves and associated fragments released by the explosive propagation of an arc flash.
- High intensity electromagnetic radiation, particularly in the ultraviolet (UV) and infrared (IR) radiation bands, but also in the visible light band, which can lead to irreversible damage to the eyes and skin.
- High levels of acoustic shock (blast).
- Toxic gases and particles produced by melting and vaporized materials in the vicinity of the arc flash (including electrodes)

Each consequence can, by itself, endanger the health and even the life of a person in proximity of the occurrence.

The most serious personal risks are associated with the thermal effects of electric fault arcing.

The PPEaA selection process used in this DGUV Information is based on the standardized Box test method according to DIN EN 61482-1-2 (VDE 0682-306-1-2)
_________

The procedures related to the selection of PPEaA tested in accordance with DIN EN 61482-1-1 (VDE 0682-306-1-1) have already been described in NFPA 70E and IEEE 1584-2018.
_________

For this reason, they are not addressed in this DGUV Information. Note Furthermore, an overview of the PPEaA selection process is included in the ISSA (International Social Security Association) “Guideline for the selection of personal protective equipment when exposed to the thermal effects of an electric fault arc” (2nd edition 2011).
_________

It is recommended to perform a Risk assessment in order to evaluate the hazards associated with electric fault arcing and to facilitate subsequent PPEaA selection. In addition to the potential severity of damage, the probability of injury due to electric arcing should also be considered as part of the analysis. Section 3 of this DGUV Information describes the approaches that can be taken with respect to the thermal effects of electric arcing.

Comprehensive examples in Annex 5 as well as exemplary depictions of work locations in Annex 6 support those who apply this DGUV Information with implementation of the Risk assessment and with the calculation process. Practical rules to apply when coordinating the selection of PPEaA with pre-fused circuits (Annex 7) point the way to finding suitable PPEaA based on the fuses used or selected.
...
add attached

Published by:
German Statutory Accident Insurance registered association (DGUV) July 2021



Info / download




Collegati
CEI 78-25 / Valutazione del rischio da arco elettrico (Arc Flash)

CEI 11-27 Ed. 6a 2025
Il rischio elettrico INAIL
CEI EN 61482-2:2022



Documenti Abbonati Sicurezza Lavoro Articoli ultimi inseriti
Documenti Abbonati Marcatura CE Articoli più letti
Documenti Abbonati Normazione Norme armonizzate
Documenti Abbonati Merci Pericolose File CEM
Documenti Abbonati Chemicals Testi consolidati
Documenti Abbonati Ambiente Vademecum
Documenti Abbonati macchine Codici
Documenti Abbonati Appunti Impianti Norme armonizzate Click
Documenti Abbonati Costruzioni Documenti Abbonati Full Plus
Documenti Abbonati Prevenzione Incendi Store





 

sono siti di:

Certifico S.r.l.
Via Antonio De Curtis 28 - 06135 Perugia - IT
Via Madonna Alta 138A - 06128 Perugia - IT
tel. +39 075 599 73 63 | +39 075 599 73 43
Assistenza 800 14 47 46

www.certifico.com
info@certifico.com

L'informativa sul trattamento dei dati personali è disponibile alla pagina Privacy.

INVIO NEWSLETTTER
Se vuoi cancellarti dall'invio della newsletter clicca qui oppure effettua il login al sito ed entra nella Tua Area Riservata, in “Modifica dati” agisci con la spunta sul box di selezione “newsletter”.


L'elenco completo di tutte le ns newsletter è qui: Archivio newsletter
 
certifico.com
Testata editoriale iscritta al n. 22/2024 registro periodici Tribunale di Perugia 19.11.2024
 
Icon Linkedin  Icona X  
Linea Footer
Certifico Srl 2000-2025 | VAT IT02442650541